Voltage Class |
24kV |
Continuous Current |
630A |
1250A* |
AC Withstand Voltage |
54kV for 5min |
Partial Discharge |
20kV,≤10pC |
Impulse Withstand Voltage(10 times for each polarity
|
125kV |
Screen Resistance |
≤5000Ω |
Screen Fault Current Initiation |
For solidly/unearthed
/impedance earthed system
|
Note: * refer to the condition when installed on an appropriate equipment bushing.

Design
1. External Screen
Moulded EPDM conductive rubber to ensure the connector touchable
2. Insulation
Moulded EPDM insulating rubber to ensure excellent electrical properties
3. Internal Screen
Moulded EPDM conductive rubber to control electrical stress
4. Two-headed Screw
To secure the conductor lug onto the bushing
5. Conductor Lug
To connect the cable conductor and bushing
6. Insulated Plug
Moulded epoxy plug having a metal insert to thread to accept the two-headed screw
7. Cable Adapter
To provide initial stress relief and watertight seal
8. Earthing Wire
To earth the external screen for the connector
9. Copper Connecting Pipe
To connect the cable lugs