1. External Screen Moulded EPDM conductive rubber to ensure the connector touchable 2. Insulation Moulded EPDM insulating rubber to ensure excellent electrical properties 3. Internal Screen Moulded EPDM conductive rubber to control electrical stress 4. Two-headed

Description
Voltage Class 12kV 17.5kV
Continuous Current 630A 1250A* 630A 1250A*
AC Withstand Voltage 28.5kV for 5min 39kV for 5min
Partial Discharge 11kV,≤10pC 15kV,≤10pC
Impulse Withstand Voltage(10 times for each polarity) 95kV 95kV
Screen Resistance ≤5000Ω ≤5000Ω

Note: * refer to the condition when installed on an appropriate equipment bushing.

 

WEBKIII 15  630.jpg

Design

1. External Screen

Moulded EPDM conductive rubber to ensure the connector touchable

2. Insulation

Moulded EPDM insulating rubber to ensure excellent electrical properties

3. Internal Screen

Moulded EPDM conductive rubber to control electrical stress

4. Two-headed Screw

To secure the conductor lug onto the bushing

5. Conductor Lug

To connect the cable conductor and bushing

6. Insulated Plug

Moulded epoxy plug having a metal insert to thread to accept the two-headed screw 

7. Cable Adapter

To provide initial stress relief and watertight seal

8. Earthing Wire

To earth the external screen for the connector

9.Copper Connecting Pipe

Connect the lugs between two cables