+86 13549360639
Language
  • English
  • Chinese

WEB 35/630

1. External Screen Moulded EPDM conductive rubber to ensure the connector touchable 2. Insulation Moulded EPDM insulating rubber to ensure excellent electrical properties 3. Internal Screen Moulded EPDM conductive rubber to control electrical stress 4. Two-headed

Description
Voltage Class 42kV
Continuous Current 630A 1250A*
AC Withstand Voltage 117kV for 5min
Partial Discharge 45kV,≤10pC

Impulse Withstand Voltage(10 times for each polarity)

200kV
Screen Resistance ≤5000Ω

Note: * refer to the condition when installed on an appropriate equipment bushing.